Sign In | Join Free | My infospaceinc.com
China Zhejiang KRIPAL Electric Co., Ltd. logo
Zhejiang KRIPAL Electric Co., Ltd.
Zhejiang KRIPAL Electric Co., Ltd 30 years experience in manufacturing ac contactor, rotary isolator switch, industrial plug socket, molded case circuit breaker and etc
Active Member

10 Years

Home > Thermal Overload Relay >

AC 3 Phase ls Thermal Overload Relay , 100A 125A Contactor Relay

Zhejiang KRIPAL Electric Co., Ltd.

AC 3 Phase ls Thermal Overload Relay , 100A 125A Contactor Relay

Brand Name : KRIPAL

Model Number : UKH-100

Certification : CE

Place of Origin : China

MOQ : 500 pcs

Price : negotiable

Payment Terms : T/T, L/C

Supply Ability : 30000 pcs per month

Delivery Time : 20 days and depends on ordering quantity

Packaging Details : Each unit packed in a individual box

Customized : color

pins : 3

type : thermal

protection : overload

Usage : Usually with ac contactor

Reset : manual / automatic

Contact Now

AC 3 Phase ls Thermal Overload Relay , 100A 125A Contactor Relay

Thermal overload relays are protective devices. They are designed to cut power if the motor draws too much current for an extended period of time. To accomplish this, thermal overload relays contain a normally closed

(NC) relay. When excessive current flows through the motor circuit, the relay opens due to increased motor

temperature, relay temperature, or sensed overload current, depending on the relay type.

These overload relays are similar to circuit breakers in construction and use, but most circuit breakers differ in

that they interrupt the circuit if overload occurs even for an instant. Thermal overload relays are conversely

designed to measure a motor's heating profile; therefore, overload must occur for an extended period before

the circuit is interrupted.

Applications:

UKH series thermal overload relay can be used in the circuit of 50Hz or 60Hz, rated insulation voltage 660V,

rated current 0.1-93A for protecting the phase break when the electric motor is overload. The relay has different mechanism and temperature compensation& can be plunged in UKC1 series AC contactor.

Specifications:

Motion Characteristic: Three-phase Balance Motion Time

No

Times of the setting current

Motion time

Start condition

Ambient temperature

1

1.05

>2h

Cold state

20±5oC

2

1.2

<2h

Heat state(Following the No.1 test)

3

1.5

<4min

4

7.2

10A

2s< Tp≤10s

≤63A

Cold state

10

4s< Tp≤10s

>63A



Phase-losing Motion Characteristic

No

Times of the setting current

Motion time

Start condition

Ambient temperature

Any two phases

Another phase

1

1.0

0.9

>2h

Cold state

20±5oC

2

1.15

0

<2h

Heat state(Following the No.1 test)

Working condition:

1. The installation altitude less than 2000m

2. The surrounding temperature range: from -5°C ~ +40°C

3. In the non-explosive condition. or without adequate erosion and destruction of gas and dust conductive area .

4. Without rain and snow invade

5. Pollution level 2

Remark:

We have two kinds of thermal overload relay: A. Old type - orange adjustable bottom;

B. New type - blue adjustable butom

AC 3 Phase ls Thermal Overload Relay , 100A 125A Contactor Relay


Product Tags:

overload protection relay

      

ls thermal overload relay

      
Quality AC 3 Phase ls Thermal Overload Relay , 100A 125A Contactor Relay for sale

AC 3 Phase ls Thermal Overload Relay , 100A 125A Contactor Relay Images

Inquiry Cart 0
Send your message to this supplier
 
*From:
*To: Zhejiang KRIPAL Electric Co., Ltd.
*Subject:
*Message: